N� <br /> DEC 012014 <br /> COMMONWEALTH of VIRGINIA <br /> Marissa J.Levine,MD,MPH,FAAFP DEPARTMENT OF HEALTH 400 S.Main Street,2nd Floor <br /> State Health Commissioner OFFICE OF DRINKING WATER Culpeper,VA 22701 <br /> John J.Aulbach II,PE Phone:540-829-7340 <br /> Director,Office of Drinking Water Culpeper Field Office Fax:540-829-7337 <br /> NOV 2 4 2014 <br /> Groundwater System Sanitary Survey Report <br /> To: Mr. Mark Whaley SUBJECT: Loudoun County <br /> 47001 Fairway Drive WATER: Algonkian Park—Pool <br /> Sterling,VA 20165 PWSID No.: 6107016 <br /> Survey Date: 10-28-2014 <br /> Present at Survey: Mark Whaley, Chris Wright and David Pinner <br /> Next Survey Scheduled For: September 2017 <br /> Future Sampling Requirements: <br /> Quarterly Entry Point Combined Nitrate/Nitrite Sample Due: 3rd Quarter 2015 <br /> Quarterly Distribution Routine Bacteriological Sample Due: 2"d Quarter 2015 <br /> As a result of the sanitary survey noted above, the Department offers the following comments. <br /> Should you have questions or desire to discuss our findings, or want a copy of the inspector's field <br /> evaluation notes, please contact us at 540-829-7340. <br /> 1. The double check valve located after the pressure tanks is leaking. Replace or repair the check <br /> valve as necessary. Please note that a check valve to prevent backflow into the well is <br /> recommended on the well discharge line prior to the pressure tanks. However, the valve does <br /> not need to be a testable device, such as a double check valve. <br /> 2. The pump house floor below the leaky double check valve is rotting and shows recent pest <br /> activity. Please repair the check valve as mentioned in comment 41 and repair the floor to <br /> prevent pests from entering the pump house. <br /> 3. Your cross connection control program was approved by this office on September 20, 2004. Be <br /> reminded, as part of that program, to inspect your distribution system at least once annually and <br /> install cross connection or backflow prevention devices as needed. At a minimum, atmospheric <br /> vacuum breakers must be installed on all threaded hose bibs that don't have built-in anti-siphon <br /> capability. If you have any "testable"devices,they must be inspected and tagged every year by <br /> a certified technician. You are required to keep records of your inspections for ten years and <br /> have them available for review upon request. <br /> vIRGINIA <br /> VDHODF EALTHNT <br /> Protecting You and Your Environment <br />